ALSECURE® H07Z1-K (AS), 1G35 mm², Green-Yellow

Descrição

Descrição

Padrões

  • Product
    EN 50525-3-31; EN 50575; IEC 60228; UNE 21022; UNE 211002
  • Installation
    NF C15-100
  • Test
    EN 50266-2-4; EN 50267-2-2; EN 50399; EN 60754-2; IEC 60332-1-2; IEC 60332-3-24; IEC 61034-2; NF C32-070/C2; UNE EN 50267-2-3 ; UNE-EN 50265-2-1

Application

Nexans H07Z1-K PROTECT Type 2 (AS) is designed for protected low-voltage fixed installations. It is suitable for the wiring of electrical panels, switchboards, control equipment, electrical apparatus and circuits installed in conduits or trunking.
Its Class 5 flexible copper conductor facilitates installation in applications requiring enhanced flexibility, such as compact switchboards, industrial and commercial cabinets, internal equipment wiring and colour-coded circuits.
The halogen-free, low-smoke insulation makes it particularly suitable for installations in buildings where fire safety requirements are critical, including public buildings, high-rise buildings, residential complexes, schools, healthcare facilities, commercial premises and protected industrial environments.

Installation

Nexans H07Z1-K PROTECT Type 2 (AS) is intended for protected indoor fixed installations in conduits, ducts, trunking systems, raceways, skirting-board trunking, mouldings or similar closed systems, either surface-mounted or concealed, in accordance with applicable installation practices and regulations. It may also be used for the internal wiring of electrical panels, switchboards, electrical apparatus and control equipment, provided compatibility with terminals and applicable wiring rules is ensured. It is not intended for direct outdoor installation, direct burial, immersion, or for mobile applications or installations subject to repeated flexing.

Recommended installation:

  • Minimum installation temperature: +5 °C
  • Minimum bending radius: 4 × D for fixed installation
  • Maximum pulling force: 50 N/mm² of copper cross-section

Características

Características

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Insulation
Halogen free, TI 7 acc. EN 50363-7
Conductor flexibility
Flexible class 5
Conductor shape
Circular
Insulation colour
Black
With Green/Yellow core
Yes
With smaller neutral conductor
No
Lead free
Yes

Características dimensionais

Características dimensionais

Conductor cross-section
35 mm²
Approximate weight
35 kg/km
Neutral conductor section (when smaller)
- mm²
Number of cores
1
Outer Diameter
- mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Max. DC resistance of the conductor at 20°C
- Ohm/km
Maximum operating voltage
750 V
Permissible current rating in open air
- A
Test voltage
2500 V

Mechanical characteristics

Mechanical characteristics

Maximum tensile strength
50 N/mm2
Cable flexibility
Flexible
Mechanical resistance to impacts
Low

Usage characteristics

Usage characteristics

Bending factor when laying
4 (xD)
Max. conductor temperature in service
70 °C
Operating temperature, range
-5 ... 70 °C
Short-circuit max. conductor temperature
160 °C
Chemical resistance
Restricted to oil, acid & base
Maximum operating temperature
70 °C
Packaging
Coil
Water proof
Limited
Weather resistance
Restricted, not ozon stable

Fire safety characteristics

Fire safety characteristics

Fire retardant
EN 50399; EN 60332-1-2
Flame retardant
EN 50265-2-1
Smoke density
IEC 61034-2
Halogen free
Yes

Recursos

Recursos

Informações de venda e entrega

Ink jet marking
USE - HAR- ALSECURE H07Z1-K (AS) TYPE 2 AENOR PLANT N° NEXANS – DAY YEAR

Entre em contato conosco

Tópicos sobre os quais você deseja obter mais informações

Campos obrigatórios*

Por favor, verifique sua entrada e tente novamente

Um endereço de e-mail deve conter um único @

Protetor de dados pessoais

Você tem o direito de se opor ao processamento de seus dados pessoais e/ou seu uso para marketing direto ou fins comerciais

Obrigado!

Obrigado por entrar em contato conosco. Retornaremos em breve.

Erro

Aconteceu um erro. Por favor, tente novamente mais tarde